|
Charging
Methods
Superheat
Method for Fixed Oriface/Capillary Tube Indoor Units-
For
fixed metering devices such as bullet orifices, pistons, and cap
tubes the superheat method will always be the method used. Measuring
superheated vapor values at the suction service valve is one of
the most important indicators of proper system performance. If
the superheat is too high, the evaporator coil will under perform.
If too low, there is a risk of damaging the compressor with liquid
refrigerant. A fixed metering device is unable to control super
heat; therefore, proper superheat values can vary greatly with
conditions that affect it, such as outdoor and indoor air conditions.
Use the steps outlined in steps 1 thru 6.
Proceed
as Follows-
1). Run the unit for at least 10 minutes to allow the system to
stabilize. Then take readings of the indoor and outdoor air temperatures
and suction pressure. Write them down.
2). On the
gauge face, read the equivalent temperature on the R-22 scale
next to the suction pressure reading.
3). Using
a thermocouple or probe type thermometer read the suction line
temperature as it enters the service valve. Make certain that
the thermocouple/probe is tight to the copper line.
4). From the
thermocouple thermometer reading subtract the suction pressure
equivalent temperature (saturated suction).
5). Proceed
to the Superheat chart (Fig. 3). Add or remove R-22 to achieve
the superheat reading indicated by the chart.
IMPORTANT: When connecting the manifold to the charging bottle
be sure to purge the hose of air with a small amount of R-22.
Wait at least
5 minutes between charge adjustments to allow the unit to stabilize.
6). When charge
adjustment is complete remove the manifold hoses from the service
valves and replace and tighten service port caps.

Chart based
on 400 cfm/ton indoor airflow and 50% relative humidity; use only
on systems that cool with an fixed oriface or capillary tube.
Sub-cooling
Method for Expansion Valve Indoor Units-
An
air conditioning system utilizing a thermostatic expansion valve
(TXV or TEV) for its metering device will automatically maintain
proper evaporator superheat regardless of varying operating conditions.
Therefore, when charging a TXV system, the charge is adjusted
to assure that there is pure liquid refrigerant, void of any flash
gas, entering the expansion device. Verifying a liquid seal
at the expansion valve can be accomplished by measuring the sub-cooling,
(sub-cooling is the sensible heat removed from the liquid refrigerant
as it travels through the last passes of the condenser). As with
superheat, the proper level of sub-cooling is important. If the
sub-cool level is too low or nonexistent, flash gas will form,
causing restricted flow through the TXV reducing system capacity.
Higher than normal sub-cooling is an indication that liquid refrigerant
is "backing up" in the condenser, reducing its effective
condensing area. If too high, due to an overcharge, it can lead
to high condensing pressure problems.
Proceed
as Follows-
1. Measure liquid line temperature and refrigerant pressure at
service valve.
2. Determine
total refrigerant pipe length and height (lift) if indoor section
is above the condenser. Plot the intersection of the two points
on Fig. 4 to determine the charging curve to use (Fig. 5).
3. Plot the
pressure and temperature on the TXV charging curve, Fig. 5.
4. If lines
cross above the curve remove refrigerant; if below curve, add
refrigerant.
5. Whenever
charge is removed or added, the system must be operated for a
minimum 20 minutes to stabilize before additional measurements
can be made.

|